ELECTRICAL GROUND
Discussions of electrical safety often center on whether circuits
are grounded. To the clinician, an electrical ground is the wire connected to the
third prong on plugs that are inserted into electrical wall outlets. With regard
to a circuit, an electrical ground is any object connected
to the circuit that is capable of instantaneously supplying or receiving arbitrarily
large amounts of electrical charge. The National Electrical Code of the National
Fire Protection Association (NFPA)
*
defines electrical ground as a conducting connection,
intentional or accidental, between an electrical circuit or equipment and earth,
or as a connection to some conducting body that serves in place of the earth. Because
the earth is an infinite reservoir of electrical charges, having a limitless ability
to give up or receive electrons, any charged object connected to earth loses its
charge and assumes the same potential as the earth.[15]
Relative to earth and to each other; the voltage between two grounded objects is
zero.
When a circuit is intentionally grounded, the physical objects
chosen to serve as the electrical ground can vary. In a remotely located Mobile
Army Surgical Hospital unit or recreational camping van, equipment may be grounded
by connections to a spike that goes into the earth. In a large urban medical center,
the ground may consist of a subterranean network of pipes. For a very small, hand-held
radio, a human being may serve as the connection to ground.
In hospital settings, the clinician does not need to understand
the details regarding the choice of ground. However, clinicians must often know
whether they, their patients, or their pieces of equipment are grounded. Living
organisms tolerate only limited amounts of electric current. Unintended contacts
with electrical ground, sometimes injurious when they enable very small electrical
currents to reach the heart or neural tissue, are always dangerous when they permit
large electric currents to travel through the body. Fortunately, it is possible
to design alarms for operating rooms and surgical equipment that provide danger signals
before errant currents are established. The line isolation monitor, which is explained
later, gives a warning when faulty ground connections are one step away from establishing
a large current in the patient. Human protection from large currents can be ensured
if connections to ground always occur through a sizable resistance. The danger of
being grounded through too small of an electrical resistance can be illustrated by
an unrealistic but vivid hypothetical example. Imagine a person standing on top
of a giant copper cylinder that extended down to the molten core of the earth. This
low-resistance connection to the largest imaginable electrical ground would be quite
unsafe because the person would essentially be a fuse, poised to suffer whatever
large electrical current is applied. The safety that would be achieved by inserting
very large electrical resistance between the person and the copper cylinder—but
not so large a resistance as to cause perfect insulation—explains a requirement
that was established long ago, when there was use of explosive anesthetic gases such
as cyclopropane. Operating rooms were then required to have conductive floors made
of specific resistive materials. Such substances had high carbon content, and they
were neither as conductive as metal nor as insulating as rubber. The high carbon
content imparted a dark black color, one that can commonly be found today in operating
room tables and cushions made of resistive materials.
In the United States, electrical plugs have three prongs: two
that provide voltage or, equivalently, power and a special third prong that serves
only as a connection to ground (i.e., to an object that makes an electrical connection
with the earth). Travelers to Europe and elsewhere may recall seeing electrical
outlets for plugs that have only two prongs and no separate ground wire. A two-wire
system becomes especially unsafe if three-pronged equipment is plugged into it, leaving
the third prong unattached to anything.
A ground fault current interruption (GFCI) electrical outlet allows
a person to test that the third connection in the outlet is connected to a functional
ground. More significantly, GFCI outlets enhance electrical safety by serving as
emergency circuit breakers that shut off power when one of the two power lines in
the outlet is accidentally connected to ground. GFCI outlets, found in hospitals
and homes, have two buttons: test and reset.
Pushing the test button causes a special resistor to be connected across the power
and ground terminals in the receptacle. If the ground connection (i.e., the third
wire) is in place and connected to the system ground, as it should be, current flows
through the resistor and causes a circuit breaker in the outlet to open. No electricity
can then be delivered by the outlet. Pushing the reset button resets the circuit
breaker and restores electrical power. Pushing the test button would not cause the
circuit breaker to open if, for example, a contractor accidentally forgot to install
the ground wire or if an earthquake or other mishap caused a break in an installed
ground wire. Protection against accidental grounding of one power line in an outlet
is required by the NFPA for wet environments, such as operating rooms. The installation
of GFCI electrical outlets is one way to satisfy NFPA protection requirements. As
is discussed later, a second way (the traditional but more expensive way) is to have
power come from an isolation transformer equipped with a line isolation monitor.
[20]
[21]
Electrical engineers commonly choose the ground as the place where
the electrical potential (voltage) is defined to be zero. Therefore, the voltage
at any point in a circuit is the difference between the voltage at that point and
the voltage at the electrical ground. Because of this, ground connections in commercial
circuits help professional personnel check for proper functioning. A technician
connects one voltmeter probe to ground while touching different circuit elements
with the other voltmeter probe. The manufacturer's table can be used to compare
readings and, in this way, identify problems in the circuit. Specifying the location
of the electrical ground helps people communicate standards for circuit performance.